Building airtightness can be defined as the resistance to inward or outward air leakage through unintentional leakage points or areas in the building envelope. This air leakage is driven by differential pressures across the building envelope due to the combined effects of stack, external wind and mechanical ventilation systems. Airtightness is the fundamental building property that impacts infiltration and exfiltration. An airtight building has several positive impacts when combined with an appropriate ventilation system :
Lower heating bills due to less heat loss, with potentially smaller requirements for heating and cooling equipment capacities
Better performing ventilation system
Reduced chance of mold and rot because moisture is less likely to enter and become trapped in cavities
A number of studies have shown substantial energy savings by tightening building envelopes. The ASIEPI project technical report on building and ductwork airtightness estimates the energy impact of envelope airtightness in the order of 10 kWh per m2 of floor area per year, for the heating needs in a moderately cold region. Experimental data showing the energy savings of good airtightness were also published by the Building Research Establishment in the UK as well as REHVA journals' special issue on airtightness. They conclude 15% of the space conditioning energy use can be saved in the UK context going from 11.5 m3/ @50 Pa down to 5 m3/ @50 Pa. Given its impacts on heat losses, good building airtightness may allow installation of smaller heating and cooling capacities. Conversely, poor airtightness may prevent achieving the desired indoor temperature conditions if the equipment has not been sized with proper estimates of infiltration heat losses. From an energy point of view, it is almost always desirable to increase air tightness, but if infiltration is providing useful dilution of indoor contaminants, indoor air quality may suffer. However, it is often unclear how useful this dilution is because building leaks cause uncontrolled airflows and potentially poorly ventilated rooms although the total building air exchange rate may be sufficient. This adverse effect has been confirmed by numerical simulations in the French context which has shown that typical mechanical ventilation systems yielded better indoor air quality with tighter envelopes. Air leaking across the envelope from the relatively warm & humid side to the relatively cold & dry side may cause condensation and related damage as its temperature drops below the dew point.
Air leakage pathways
Leakage typically occurs at the following locations on the building envelope:
Junctions between walls and other walls or floors
Junctions between window frames and walls
Electrical equipment
Access doors and other wall penetrations
Common leakage sites are listed in the Figure and explained below:
The airtightness of a building is often expressed in terms of the leakage airflow rate through the building's envelope at a given reference pressure divided by the:
Heated building volume V. At 50·Pa, it is called the air change rate at 50 Pa and usually noted n50.
Envelope area AE. At 50 Pa, it is called the air permeability at 50 Pa and noted usually q50 or qa50
Floor area AF. At 50 Pa, it is called the specific leakage rate and usually noted w50
The effective leakage area at a reference pressure is also a common metric used to characterize envelope airtightness. It represents the area of a perfect orifice that would produce the same airflow rate as that passing through the building envelope at the reference pressure. To allow comparisons between buildings, the ELA may be divided by the envelope or floor area, or may be used to derive the normalized leakage area. For all of these metrics, the lower the 'airtightness' value is for a given building, the more airtight the building's envelope is.
Power law model of airflow through leaks
The relationship between pressure and leakage air flow rate is defined by the power law between the airflow rate and the pressure difference across the building envelope as follows: qL=CL∆pn where:
qL is the volumetric leakage airflow rate expressed in m3h−1
CL is the air leakage coefficient expressed in m3h−1Pa−n
∆p is the pressure difference across the building envelope expressed in Pa
n is the airflow exponent
This law enables to assess the airflow rate at any pressure difference regardless the initial measurement.
Fan pressurization test
Building airtightness levels can be measured by using a fan, temporarily installed in the building envelope to pressurize the building. Air flow through the fan creates an internal, uniform, static pressure within the building. The aim of this type of measurement is to relate the pressure differential across the envelope to the air flow rate required to produce it. Generally, the higher the flow rate required to produce a given pressure difference, the less airtight the building. The fan pressurization technique is also described in many standard test methods, such as ASTM E779 - 10, ASTM E1827 – 11, CAN/CGSB-149.10-M86, CAN/CGSB-149.15-96, ISO 9972:2006, & EN 13829 which is now 'withdrawn' due to the updated ISO 9972:2015.
Airtightness requirements
Most European countries include in their regulations either required or recommended minimum airtightness levels with or without mandatory testing. There are several countries where, by regulation, airtightness testing is mandatory for certain building types or in the case of specific programmes. In the US, the IECC of 2012 adopted whole building airtightness requirements, including mandatory testing. In addition, in May, 2012, USACE issued a new Engineering and Construction Bulletin in collaboration with the , outlining Army requirements for building airtightness and building air leakage testing for new and renovation construction projects. Washington was the first State to institute air barrier requirements with both a maximum material air leakage requirement and a whole building maximum air permeability rate with testing requirements for buildings six stories and higher. There are several voluntary programs that require a minimum airtightness level for the building envelope. Historically, the Passivhaus standard, originated in 1988 was the cornerstone for envelope airtightness developments because these types of buildings require extremely low leakage levels.